首页 | 本学科首页   官方微博 | 高级检索  
     检索      

高温气冷堆核电站主氦风机驱动电机绝缘系统评定技术研究
引用本文:汪双灿,黄慧洁,管兆杰.高温气冷堆核电站主氦风机驱动电机绝缘系统评定技术研究[J].航空动力学报,2018,45(3):108-111, 116.
作者姓名:汪双灿  黄慧洁  管兆杰
作者单位:[上海电器科学研究所集团有限公司,上海200063],[上海电器科学研究所集团有限公司,上海200063],[上海电器科学研究所集团有限公司,上海200063]
摘    要:设计了一套在0.1 MPa氦气和空气环境下测试绝缘系统电气绝缘性能的试验装置,完成了0.1 MPa气压下氦气和空气中主氦风机驱动电机绝缘系统模型的局部放电起始电压(PDIV)、起晕电压、匝间冲击、绝缘电阻和工频击穿电压对比试验。试验结果表明:在0.1 MPa气压下,绝缘系统在氦气环境下的部分绝缘性能较空气中大幅下降,氦气环境下绝缘系统的PDIV值约为空气中的50%,起晕电压值约为空气中的20%~25%, 闪络(击穿)电压约为空气中的50%。

关 键 词:主氦风机驱动电机    绝缘系统    局部放电起始电压    起晕电压

Assessment Technology Research of Insulation Systems of Helium Circulator Drive Motor for HighTemperature Gascooled Reactor Nuclear Power Plant
WANG Shuangcan,HUANG Huijie and GUAN Zhaojie.Assessment Technology Research of Insulation Systems of Helium Circulator Drive Motor for HighTemperature Gascooled Reactor Nuclear Power Plant[J].Journal of Aerospace Power,2018,45(3):108-111, 116.
Authors:WANG Shuangcan  HUANG Huijie and GUAN Zhaojie
Institution:[Shanghai Electrical Apparatus Research Institute Group., Ltd., Shanghai 200063, China],[Shanghai Electrical Apparatus Research Institute Group., Ltd., Shanghai 200063, China] and [Shanghai Electrical Apparatus Research Institute Group., Ltd., Shanghai 200063, China]
Abstract:A test apparatus that testing for the electrical insulation properties of the insulation systems under 0.1 MPa helium and air environment respectively was designed. Partial discharge inception voltage (PDIV), corona inception voltage, interturn impact, insulation resistance and power frequency breakdown voltage of insulation system model for helium circulator drive motor under 0.1 MPa helium and air environment respectively were tested. Test showed that some insulating properties of the insulation system in helium environment dropped significantly compared with that in the air environment at 0.1 MPa pressure, PDIV of insulation system in helium environment is about 50% of that in the air environment, corona inception voltage of insulation system in helium environment is about 20% to 25% of that in the air environment, flashover breakdown voltage of insulation system in helium environment is about 50% of that in the air environment.
Keywords:helium circulator drive motor  insulation systems  partial discharge inception voltage (PDIV)  corona inception voltage