基于无功相对偏差的无刷励磁发电机转子绕组匝间短路故障诊断新判据
引用本文:沈利平,马明晗,李永清,马春泉,冯雪萍.基于无功相对偏差的无刷励磁发电机转子绕组匝间短路故障诊断新判据[J].航空动力学报,2017,44(11):106-110, 117.
作者姓名:沈利平  马明晗  李永清  马春泉  冯雪萍
作者单位:国家电网甘肃省电力公司 刘家峡水电厂,甘肃 永靖731600,华北电力大学 电气与电子工程学院,河北 保定071003,国家电网甘肃省电力公司 刘家峡水电厂,甘肃 永靖731600,国家电网甘肃省电力公司 刘家峡水电厂,甘肃 永靖731600,国家电网甘肃省电力公司 刘家峡水电厂,甘肃 永靖731600
摘    要:为了寻找到在线识别无刷励磁同步发电机转子匝间短路故障的新方法,通过对同步发电机发生转子绕组匝间短路后电磁特性和电气参量的变化进行分析,根据故障发生后励磁电流增加而无功输出量却相对减少的特征,提出了利用计算和测量故障前后发电机输出无功相对变化率,作为识别无刷励磁同步发电机转子匝间短路故障严重程度的一个较为实用的方法。利用发电机动态模拟试验机组,进行了相关的试验验证。

关 键 词:无刷励磁同步发电机  转子绕组匝间短路  故障诊断判据  无功功率  相对偏差

New Criterion on Rotor Windings Inter Turn ShortCircuit Fault Diagnose ofBrushless Excitation Generator Based on Reactive Power Relative Deviation
SHEN Liping,MA Minghan,LI Yongqing,MA Chunquan and FENG Xueping.New Criterion on Rotor Windings Inter Turn ShortCircuit Fault Diagnose ofBrushless Excitation Generator Based on Reactive Power Relative Deviation[J].Journal of Aerospace Power,2017,44(11):106-110, 117.
Authors:SHEN Liping  MA Minghan  LI Yongqing  MA Chunquan and FENG Xueping
Institution:Liujiaxia Hydropower Plant, Gansu Electric Power Company of State Grid Corporation of China,Yongjing 731600, China,Electrical and Electronic Engineering, North China Electric Power University, Baoding 071003, China,Liujiaxia Hydropower Plant, Gansu Electric Power Company of State Grid Corporation of China,Yongjing 731600, China,Liujiaxia Hydropower Plant, Gansu Electric Power Company of State Grid Corporation of China,Yongjing 731600, China and Liujiaxia Hydropower Plant, Gansu Electric Power Company of State Grid Corporation of China,Yongjing 731600, China
Abstract:In order to find a new method to the online identification of inter turn shortcircuit fault of brushless excitation synchronous generator rotor, the change of electromagnetic properties was analysed and electrical parameters after the synchronous generator rotor windings occurred inter turn shortcircuit. According to the characteristic that the exciting current was increasing and the reactive power output was decreasing relatively, a method was put forward which uses generator reactive power output relative change rate which was calculated or measured before and after the fault as a practical criterion for identification of the severity of brushless excitation synchronous generator rotor windings inter turn shortcircuit fault. Finally, the relative experiment was carried out using the dynamic analog experiment unit.
Keywords:brushless excitation synchronous generator  rotor windings inter turn shortcircuit  fault diagnosis criterion  reactive power  relative deviation