Single-phase power distribution system power flow and faultanalysis |
| |
Authors: | Halpin S.M. Grigsby L.L. |
| |
Affiliation: | Dept. of Electr. Eng., Auburn Univ., AL; |
| |
Abstract: | Alternative methods for power flow and fault analysis of single-phase distribution systems are presented. The algorithms for both power flow and fault analysis utilize a generalized approach to network modeling. The generalized admittance matrix, formed using elements of linear graph theory, is an accurate network model for all possible single-phase network configurations. Unlike the standard nodal admittance matrix formulation algorithms, the generalized approach uses generalized component models for the transmission line and transformer. The standard assumption of a common node voltage reference point is not required to construct the generalized admittance matrix. Therefore, truly accurate simulation results can be obtained for networks that cannot be modeled using traditional techniques |
| |
Keywords: | |
|
|