首页 | 本学科首页   官方微博 | 高级检索  
     检索      

串列双U型管束换热器压降与回热效率模型实验
引用本文:刘喜岳,张靖周,李刚团,康涌.串列双U型管束换热器压降与回热效率模型实验[J].航空学报,2017,38(3).
作者姓名:刘喜岳  张靖周  李刚团  康涌
作者单位:1. 南京航空航天大学能源与动力学院,江苏省航空动力系统重点实验室,南京 210016;2. 南京航空航天大学能源与动力学院,江苏省航空动力系统重点实验室,南京 210016;先进航空发动机协同创新中心,北京 100083;3. 中国燃气涡轮研究院,成都,610500
摘    要:为了研究串列双U型管束换热器的流动和传热特性,开展了模型实验,得到了串列双U型管束换热器布置方式对喷管通道流动压降和换热器回热效率的影响。结果表明:喷管通道流动压降随着换热器安装角的增大而增加,邻近喷管收敛状出口位置的换热器安装角对流动压降的影响最为显著,进口附近的换热器影响次之;相对通道内置单个换热器的情形,串列换热器中前置换热器安装角的变化对流动压降的影响有所减弱;较小的前置换热器安装角度导致其回热效率过低,从而导致平均回热效率难以改善;在本文研究的几种布置方式下,安装角为30°-17°-13°的串列换热器布置方式的流动和传热综合性能相对较优。

关 键 词:U型管换热器  串列布置  安装角  压降  回热效率  模型实验

Model experiment on pressure drop and thermal recovery efficiency of tandem double-U-shaped-tube heat exchangers
LIU Xiyue,ZHANG Jingzhou,LI Gangtuan,KANG Yong.Model experiment on pressure drop and thermal recovery efficiency of tandem double-U-shaped-tube heat exchangers[J].Acta Aeronautica et Astronautica Sinica,2017,38(3).
Authors:LIU Xiyue  ZHANG Jingzhou  LI Gangtuan  KANG Yong
Abstract:In order to investigate the flow and heat transfer performances of tandem double-U-shaped-tube heat exchangers,model experiments are conducted.The effects of arrangement of the tandem heat exchangers on the nozzle pressure drop and recuperator effectiveness are obtained.The results show that the nozzle pressure drop is increased with the increase of heat exchanger inclined angle.The inclined angle of the last heat exchanger adjacent to the convergent nozzle exit has the most significant influence on the nozzle pressure drop,and the influence of the front heat exchanger adjacent to the nozzle inlet comes the second.In comparison with the situation where a single heat exchanger is placed inside the nozzle,the influence of the inclined angle of the front heat exchanger on pressure drop is slightly weakened when tandem heat exchangers is used.When the inclined angle of the front heat exchanger is small,the thermal recovery efficiency achieved by the front heat exchanger is very low,thus making it difficult to improve the overall thermal recovery efficiency of tandem heat exchangers.Among several arrangements of tandem heat exchangers in the present tests,the inclined angles of 30°-17°-13° corresponding to the three tandem heat exchangers appears to be more reasonable for obtaining the optimum comprehensive flow and heat transfer performance.
Keywords:U-shaped-tube heat exchanger  tandem arrangement  inclined angle  pressure drop  thermal recovery efficiency  model experiment
本文献已被 CNKI 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号